Product specification:
 
1. Current Rating: 400 A to 6300 A(CU) or 100A to 4000A(AL)
 
2. Ingress protection of IP54 or IP65
 
3. Insulation curent rating: [upto 1000 A]
 
4. Standard lengths of 4m/3m/2m/1m
 
5. System Voltage: AC380 /690V
 
6. Conductor material: High conductivity Cu or AL
 
7. Halogen free, fire retardant Class-B-Epoxy insulation
 
8. Tap - off units are suitable for MCCBs or SDFs or MCBs
 
Product instroduction:

Busbar system for electrical distribution is an alternative to cumbersome conventional cable distribution system. 
Decentralized distribution is the main highlight of this distribution system.
This system eliminates separate requirement of distribution & panel boards.
Loads can be fed from Plug-in Boxes unlike cables where each floor /machine is to be fed separately from the main switchboard. 
Can be installed quickly with minimum technical expertise and have good asthetics.
Any section of bustrunking can be removed without distrurbing adjacent sections.
System is maintenance free and adds elegance to the surrounding. 
 
Sandwich busbar trunking system main features
low reactance, low impedance, low voltage drop and low power loss. 
Due to elimination of air there is no rise of chimney effect, so no fire barriers are required.
Due to compactness system can be installed in lesser space.
Automatic polarity is maintained during installation. 
System can be mounted edgewise OR flat wise, horizontally or vertically in any direction with all kinds of bends and tees etc. 
Flexible and safe distribution system leads to easy and fast installation.
System is completely re-usable. 

Technical Parameters :

Rated current (A)
Earthing bar resistance (10-6Ω/m)
Copper conductor  AL conductor 
100 368.3 404.7
160 368.3 404.7
200 368.3 404.7
250 368.3 404.7
400 248 306.8
500 213.6 248.8
630 213.6 210.3
800 168.2 163
1000 139.5 141
1250 112.3 112.5
1350 96.6 101.7
1600 82.8 90.8
2000 66.5 74.8
2300 54.6 66.6
2500 44.9 62.2
3150 34.5 40.2
3800 29.6 33.3
4000 27.9 31.1
4500 22.5 /
5000 20.5 /
 

Main componnets:

Feeder Bustrunking
Plug-in Busbar trunking
Joint block
Horizontal Elbow
Horizontal Offset [Z] Elbow
Vertical Elbow
Vertical Offset [Z] Elbow
Vertical Tee Section
Standard Flange End
Flange End Box cum Termination Detail
MCCB Plug-in Boxes