TitleProduct

Xmtc-608 LED Temperature Regulator with Two Row Display

  • Price:

    Negotiable

  • minimum:

  • Total supply:

  • Delivery term:

    The date of payment from buyers deliver within days

  • seat:

    Zhejiang

  • Validity to:

    Long-term effective

  • Last update:

    2017-10-21 11:56

  • Browse the number:

    257

Send an inquiries

Company Profile

Yuyao Gongyi Meter Co., Ltd.

By certification [File Integrity]

Contact:Ms. Vera(Mr.)  

Email:

Telephone:

Phone:

Area:Zhejiang

Address:Zhejiang

Website: http://yuyaogongyi.kskuntai.com/

Product Details


Specifications

Temperature controller
On/off
PID control
Temperature meter are dual row 3-LED display
Input: CU50; PT100; J; E; K; T



XMT*608 series intelligent temperature controller, is double row 3-LED display and include on/off, PID control, including with parameter of self-setting function. This temperature meter respectively display temperature measurement value (PV) and temperature set value (SV) under normal mode; When it is time temperature control, respectively display temperature measurement value (PV) and running time count down (SV), and also provide kinds of time control method selection; The controller can input kinds of signal which are used interchangeably, it adopt ON/OFFP=0PID control, allowing an easy parameter setting and convenient inputting, is widely used over temperature automatic control systems of machinerychemicalceramicslight industrialmetallurgypetrifaction and heat treatment and so on.

Main technical Indexes

1, Measurement deviation: ± 0.5%F· S± 1B, Cold end compensating deviation≤ ± 2C
2, Input(can be selected): CU50(-50~150), PT100(-199~600), K(-30~999),
E(-30~700), J(-30~900), T(199~400)
3, Relay output contact capacity: AC220V 5A(resistance load)
Period 2~120s can be adjusted.
4, Drivng solid relay signal output: Driving electric current >15m A voltage >9V,
Period is 2S
5, Power: AC85V~242V, 50/60Hz
6, Work environment: Temperature 0~50.0C, relative humidity≤ 85%RH, without corrode and strong electric radiation.

Instrument panel(consult)
 






Connection scheme(consult)















 
Series Code Name Setting range Remark Ex-Factory
 
 
 
 
 
First 
 
 
 
 
 
 
 
 
 
Menu
 
 
0
 
-
Appointed data Determined
by
and 
Press∧or∨for 3 second and set the temperature setting value you need   
-
 
1
 AL
 
High/Low-limit 
alarm
Determined
by
and 
 
-
 
Random
2 SC Measurement
deviation
-20.0~20.0 Measuring value can be modified through increasing or decreasing this data. 0
 
3
 P
 
 
Proportion time
0~99.9~200 When the P↑,the proportion and differential
function↓;If the P↓,the proportion and 
differential function↑
When P=0,the meter is ON/OFF control.
15.0
 
4
 I
 
 
Calculus time
0~999 It's used to adjust static difference. To increse it,the static difference will be reduced, but if it is too high, the static difference will drift instability. 240
5  d Differential time 0~200
 
30
 
6
 
 t
 
Control period 
 
2~120S
When it leaves factory, SSR is 2s;
Relay is 20s. 
When P=0, it makes no sense.
 
20
 
7
 
 Hy
Main control by drop in level  
0.1~50.0
 
It only controls at ON/OFF
 
1.0
 
8
 At
 
 
Parameter setting itself
 
/
OFF_shut itself function ;
ON_open itself function
Select ' ON'only can adjust for one time,and then turn back to 'OFF '
 
 OFF
 
9
 Loc
 
Electronics
lock
 
0~50
 Loc=0 all the parameter can be revised 
 Loc=1 only the appointed data can be revised
 
0

 
 
 
 
Second 
 
 
 
 
 
 
 
Menu
 
10  Loc Electronics
lock
0~50 idem 0
11  Sn Input type - CU50\PT100\K\E\J(\T; K
 
12
 
 dIL
 
Set lower limit
 
 
dIL≤dIH
CU50(-50~150)\
PT100(-80~600)\
K(-30~999)\E(-30~700)\
J(-30~900)\T(199~400)
 
 
0
 
13
 
 dIH
 
Set upper limit
 
400
 
 
14
 
 PF
 
 
 
Filt modulus
 
 
0~50
It is the software filter constant of measurement sampling.The constant ↑,the measurement antijamming capability↑,but the measurement speed and system response time ↓  
 
20
15  COL System function 
choice
 
ON/OFF
ON:positive control(cooling control)
OFF:reverse control(heating control)
 
 OFF


Packaging Details