Product Details
CURRENT RANSFORMER 0.72 Kv,
TYPE SPLIT CORE, 60 Hz , 300/5 A, CLASS 1,
ÍTEM SAP:270102
Ratio (A)
|
300/5 |
Voltage of operatión (kV) |
0.23/0.38/0.44 |
ÍTEM |
CHARACTERÍSTICS |
UNIT |
REQUIRED |
GUARANTEED |
1 |
General Characterístics |
|
|
|
1.1 |
COUNTRY |
------ |
Indicate |
CHINA |
1.2 |
MANUFACTURER |
------ |
Indicate |
HEMG |
1.3 |
MODEL |
------ |
Indicate |
LMZK-0.72 |
1.4 |
STANDARD |
------ |
IEC 61869-1 (2007); IEC 61869-2 (2012)
|
IEC 61869-1 (2007); IEC 61869-2 (2012)
|
1.5 |
APPLICATION |
------ |
MEASURE |
MEASURE |
2 |
Nominal data and characterístics |
|
|
|
2.1 |
FREQUENCY |
Hz |
60 |
60Hz |
2.2 |
TYPE |
------ |
SPLIT CORE
|
SPLIT CORE |
2.3 |
MOUNTING |
------ |
INDOOR |
INDOOR |
2.4 |
INSULATION LEVEL |
|
|
|
|
MAX. VOLTAGE OF OPERATION |
kV |
0.72 |
0.72kV |
|
VOLTAGE WITH INDUSTRIAL FREQUENCY, 1 MINUTE SECONDARY |
kV |
3 |
3Kv |
2.5 |
CURRENTS |
|
|
|
|
Nominal secondary current (Isn) |
A |
5 |
5 A |
|
Nominal primary current (Ipn) |
A |
300 |
300 A |
|
Nominal thermal current of shortcircuit (Ith), IEC 61869-2
|
A |
60 Ipn |
60 Ipn |
|
Nominal dynamic current (Idyn) IEC 61869-2
|
A |
2.5 Ith
|
2.5 Ith
|
2.6 |
Ratio of transformatión
|
A |
300/5 |
300/5A |
2.7 |
Power |
VA |
2.5 |
2.5VA |
2.8 |
Precision class |
cl |
1 |
1 |
2.9 |
Class thermal of insulation (IEC 60085)
|
|
E |
E |
2.10 |
Factor of security |
|
5 |
5 |
2.11 |
Guarantee the precisión class in the range |
|
from 25%Isn to 100% Isn
|
from 25%Isn to 100% Isn
|
3 |
Accesories |
|
|
|
3.1 |
Fixation to the base |
------ |
yes |
YES |
3.2 |
Fixation to rail DIN |
------ |
yes |
YES |
3.3 |
Dimensions mínimum for the primary |
mm x m m |
Indicate
|
DIA 50mm |
3.4 |
Metallic nameplate with tech nicall characterístics and scheme of connection
|
------ |
yes
|
YES |
3.5 |
Sealable terminals, with holes of sufficient diamet er to pass through the thread of th e seal
|
------ |
yes
|
YES |
3.6 |
Grounding Terminals
|
|
yes
|
YES |
3.7 |
Presents th e Certificate and Protocol of type tests of compliance of the standard IEC 61869-2
|
|
Yes
|
YES |
CURRENT RANSFORMER 0.72 Kv,
TYPE SPLIT CORE, 60 Hz , 400/5 A, CLASS 1
ÍTEM SAP: 270201
Ratio (A)
|
400/5 |
Voltage of operatión (kV) |
0.23/0.38/0.44 |
ÍTEM |
CHARACTERÍSTICS |
UNIT |
REQUIRED |
GUARANTEED |
1 |
General Characterístics |
|
|
|
1.1 |
COUNTRY |
------ |
Indicate |
CHINA |
1.2 |
MANUFACTURER |
------ |
Indicate |
HEMG |
1.3 |
MODEL |
------ |
Indicate |
LMZK-0.72 |
1.4 |
STANDARD |
------ |
IEC 61869-1 (2007); IEC 61869-2 (2012)
|
IEC 61869-1 (2007); IEC 61869-2 (2012)
|
1.5 |
APPLICATION |
------ |
MEASURE |
MEASURE |
2 |
Nominal data and characterístics |
|
|
|
2.1 |
FREQUENCY |
Hz |
60 |
60Hz |
2.2 |
TYPE |
------ |
SPLIT CORE
|
SPLIT |
2.3 |
MOUNTING |
------ |
INDOOR |
INDOOR |
2.4 |
INSULATION LEVEL |
|
|
|
|
MAX. VOLTAGE OF OPERATION |
kV |
0.72 |
0.72kV |
|
VOLTAGE WITH INDUSTRIAL FREQUENCY, 1 MINUTE SECONDARY |
kV |
3 |
3Kv |
2.5 |
CURRENTS |
|
|
|
|
Nominal secondary current (Isn) |
A |
5 |
5 A |
|
Nominal primary current (Ipn) |
A |
400 |
400 A |
|
Nominal thermal current of shortcircuit (Ith), IEC 61869-2
|
A |
60 Ipn |
60 Ipn |
|
Nominal dynamic current (Idyn) IEC 61869-2
|
A |
2.5 Ith
|
2.5 Ith
|
2.6 |
Ratio of transformatión
|
A |
400/5
|
400/5A |
2.7 |
Power |
VA |
5, 7.5,10 |
5VA |
2.8 |
Precision class |
cl |
1 |
1 |
2.9 |
Class thermal of insulation (IEC 60085)
|
|
E |
E |
2.10 |
Factor of security |
|
5 |
5 |
2.11 |
Guarantee the precisión class in the range |
|
from 25%Isn to 100% Isn
|
from 25%Isn to 100% Isn
|
3 |
Accesories |
|
|
|
3.1 |
Fixation to the base |
------ |
yes |
YES |
3.2 |
Fixation to rail DIN |
------ |
yes |
YES |
3.3 |
Dimensions mínimum for the primary |
mm x mm |
Indicate
|
DIA 50mm |
3.4 |
Metallic nameplate with technicall characterístics and scheme of connection
|
------ |
yes |
YES |
3.5 |
Sealable terminals, with holes of sufficient diameter to pass through the thread of the seal
|
------ |
yes |
YES |
3.6 |
Grounding Terminals
|
|
yes
|
YES |
3.7 |
Presents the Certificate and Protocol of type tests of compliance of the standard IEC 61869-2
|
|
Yes |
YES |
CURRENT RANSFORMER 0.72 Kv,
TYPE SPLIT CORE, 60 Hz , 600/5 A, CLASS 1
ÍTEM SAP: 27020
Ratio (A)
|
600/5 |
Voltage of operatión (kV) |
0.23/0.38/0.44 |
ÍTEM |
CHARACTERÍSTICS |
UNIT |
REQUIRED |
GUARANTEED |
1 |
General Characterístics |
|
|
|
1.1 |
COUNTRY |
------ |
Indicate |
CHINA |
1.2 |
MANUFACTURER |
------ |
Indicate |
HEMG |
1.3 |
MODEL |
------ |
Indicate |
LMZK-0.72 |
1.4 |
STANDARD |
------ |
IEC 61869-1 (2007); IEC 61869-2 (2012)
|
IEC 61869-1 (2007); IEC 61869-2 (2012)
|
1.5 |
APPLICATION |
------ |
MEASURE |
MEASURE |
2 |
Nominal data and characterístics |
|
|
|
2.1 |
FREQUENCY |
Hz |
60 |
60Hz |
2.2 |
TYPE |
------ |
SPLIT CORE
|
SPLIT CORE |
2.3 |
MOUNTING |
------ |
INDOOR |
INDOOR |
2.4 |
INSULATION LEVEL |
|
|
|
|
MAX. VOLTAGE OF OPERATION |
kV |
0.72 |
0.72kV |
|
VOLTAGE WITH INDUSTRIAL FREQUENCY, 1 MINUTE SECONDARY |
kV |
3 |
3Kv |
2.5 |
CURRENTS |
|
|
|
|
Nominal secondary current (Isn) |
A |
5 |
5 A |
|
Nominal primary current (Ipn) |
A |
600 |
600 A |
|
Nominal thermal current of shortcircuit (Ith), IEC 61869-2
|
A |
60 Ipn |
60 Ipn |
|
Nominal dynamic current (Idyn) IEC 61869-2
|
A |
2.5 Ith
|
2.5 Ith
|
2.6 |
Ratio of transformatión
|
A |
600/5 |
600/5A |
2.7 |
Power |
VA |
5, 7.5,10 |
5VA |
2.8 |
Precision class |
cl |
1 |
1 |
2.9 |
Class thermal of insulation (IEC 60085)
|
|
E |
E |
2.10 |
Factor of security |
|
5 |
5 |
2.11 |
Guarantee the precisión class in the range |
|
from 25%Isn to 100% Isn
|
from 25%Isn to 100% Isn
|
3 |
Accesories |
|
|
|
3.1 |
Fixation to the base |
------ |
yes |
YES |
3.2 |
Fixation to rail DIN |
------ |
yes |
YES |
3.3 |
Dimensions mínimum for the primary |
mm x mm |
Indicate
|
DIA 50mm |
3.4 |
Metallic nameplate with technicall characterístics and scheme of connection
|
------ |
yes |
YES |
3.5 |
Sealable terminals, with holes of sufficient diameter to pass through the thread of the seal
|
------ |
yes |
YES |
3.6 |
Grounding Terminals
|
|
yes
|
YES |
3.7 |
Presents the Certificate and Protocol of type tests of compliance of the standard IEC 61869-2
|
|
Yes |
YES |