Product Details
0.333-3.53V split core current transformer with core current
TIANJIN GREWIN TECHNOLOGY CO.,LTD. |
GWCTSA series split core current transformer |
Part number |
Rated input(A) |
Second output(V) |
Accuracy class |
Limit primary current(A) |
Accuracy class |
Frequency(Hz) |
OutlineDimensions ID-L-W-H(mm) |
Unit weight |
Turn ratio |
Output cable |
GWCTSA005 |
5 10 15 |
0.333 |
1.0 3.0 |
- |
- |
50-400 |
5.0-25.0-22.5-34.5 |
30g |
3000:1 |
wire(1m) |
GWCTSA010 |
5,10,20,50,75 |
0.333 |
1.0 3.0 |
120 |
5P 10P |
50-400 |
10-29.4-26.4-41.7 |
50g |
3000:1 |
wire(1m) |
GWCTSA016 |
75,100,150 |
0.333 |
0.5 1.0 |
300 |
5P 10P |
50-400 |
16-36.9-39.2-52.9 |
100g |
3000:1 |
wire(1m) |
GWCTSA024 |
100,150,200,250 |
0.333 |
0.5 1.0 |
540 |
5P 10P |
50-400 |
24-51.2-47-70.2 |
250g |
3000:1 |
wire(1m) |
GWCTSA035 |
200,300,400,600 |
0.333 |
0.5 1.0 |
600 |
5P 10P |
50-400 |
35-65.8-51.2-83.5 |
400g |
3000:1 |
wire(1m) |
GWCTSA Series Split Core Current Sensor (Specifications)
|
Rated Primary current
|
5-600A
|
Rated Secondary current
|
0.333V-3.53V
|
Rated load
|
1, 2.5, 5.0, 10, 30VA
|
Accuracy
|
0.5, 1.0, 3.0 Class
|
Rated Short-time thermal current (Ith)
|
20In
|
Rated Dynamic current (Idyn)
|
2.5Ith
|
Case Material
|
UL flame retardant rating 94-V0
|
Highest Voltage for Equipment Um (rms)
|
720 Vac
|
Rated Power-Frequency Withstand Voltage(rms)
|
3,000 Vac
|
Frequency Range:
|
50/60Hz
|
Operating Temperature
|
-15ºC to 50ºC
|
Standard
|
IEC 60044-1
|
Accessories
|
Supplied with feet for base mounting if required
|
Certification
|
RoHS compliant CE&ETL approved
|
GWCTSA Series Split Core Current Sensor (Features)
|
Low cost
|
5 standard sizes
|
Split core design, safer, easier installation, and portable
|
GWCTSA Series Split Core Current Sensor (Applications)
|
Measures AC current flow to electric motors, lighting, air condition equipment, etc.
|
Compatible with HVACtemperature control, power management, building
|
The GREWIN CTSA series of split core ct style current sensors are designed for fast and easy installation.The split core design permits non-contactcurrent measurements through magnetic field induction without disconnecting cables or busbar circuits for CT installation. This method permits a safer, easier and portable current measurement.
0.333-3.53V rated secondary output split core current transformer :
Model No 1 :GWCTSA010
Ratio : 3000:1
Rated input: 5A 10A 20A 50A 75A
Accuracy class: 1.0s 3.0s
Rated primary current :120A
Protection: 5 times protection ,10 times protection like 25A 50A 100A 200A 250A 385A 500A 750A
Model No.2 :GWCTSA016
Ratio :3000:1
Rated input: 75A 100A 150A
Accuracy class: 0.5 1.0S
Rated accuracy limit primary current: 300A
Protection : 5 times Protection, 10 times protection
Model No. 3:GWCTSA024
Ratio : 3000:1
Rated input: 100A 150A 200A 250A
Accuracy class: 0.5 1.0S
Rated accuracy limit primary current: 540A
Protection : 5 times Protection, 10 times protection
Model No.4:GWCTSA035
Rated input: 200A 300A 400A 600A
Accuracy class: 0.5 1.0S
Rated accuracy limit primary current: 600A
Protection : 5 times Protection, 10 times protection
Frequency: 50--400Hz
Aliceli
Tianjin Grewin Technology Co.,Ltd.
Website: